The harvest in the air

If not controlled correctly, excess dust and gases that form inside silos, bulk carriers and hoppers can cause fires or explosions that, in addition to destroying the grain mass, can destroy compost.

10.11.2015 | 21:59 (UTC -3)

One of the priority issues, in Storage Units, concerns accidents that occur caused by the most different reasons, mainly due to human or operational errors. Other accidents occur due to environmental risks, especially pollution, dust, aerosols and poisonous and explosive gases.

There is particularly a very serious situation, with losses of products, equipment, silos and other buildings, which occur due to excess dust and gases that form inside the silo battery galleries, bulk carriers, elevator shafts and hoppers. .

Agricultural grain dust is produced during harvesting, drying, handling, storage and industrialization, due to various frictions. In addition to the intrinsic properties of the dust, it may contain contaminating particles that can be harmful to human health.

The amount of dust produced by a mass of grains is related to its constitution, physical characteristics and state of conservation, being influenced by the relationship between the quantity of whole and broken grains, the presence of insects, impurities, etc. During movement, 0,1 to 1% of the volume of processed grains turns into powder.

Explosions in storage plants can be classified as primary and secondary. Dust deposited over time in the most diverse locations of the industrial plant, when shaken or placed in suspension and in the presence of an ignition source, with sufficient energy for the first deflagration, may explode, causing subsequent vibrations due to the shock wave; causing more deposited dust to come into suspension and more explosions to occur, each one more devastating than the previous one, causing irreversible damage to property, interruptions in the production process, disability or death.

The change from fire to explosion can occur easily, as long as dust deposited in the vicinity of the fire is agitated, comes into suspension, gains minimal concentration, and as the site already has the necessary ingredients, the next step is to trigger subsequent explosions. . Conversely, if suspended dust causes an explosion, the burning dust particles come out of suspension and spread the fire. In these terms, the damage could be much greater.

The possibility of a dust cloud exploding is conditioned by the size of its particles, their concentration, impurities, oxygen concentration and the power of the ignition source. Dust explosions often occur in series; Often the initial deflagration is very small in quantity, but of sufficient intensity to put surrounding dust into suspension, or rupture parts of machines or installations within the building, such as dust collectors, creating a larger cloud through from which secondary explosions can spread and even from one building to another.

The danger of a given class of dust is related to its ease of ignition and the severity of the resulting explosion.

Particles smaller than 100 microns adhere to the grains during the cleaning operation and may become detached during movement and, therefore, remain in suspension. Studies reveal that particles smaller than 100 microns take more than 24 hours to settle into two cm. The powder particles have the following properties: moisture content – ​​5 to 11% bu, carbohydrates – 6 to 20%, lipids – 1 to 4% and fibers 7 to 15%.

Like gases and vapors, agricultural dust requires concentration limits for different particle sizes suspended in the air so that explosions or fires can occur. Other factors can change the dust concentration index, including particle size and diameter, oxygen concentration, energy of the ignition source; the turbulence of the dust cloud and the purity content of the dust.

Preventive measures, such as controlling the concentration of dust in the environment, warnings prohibiting smoking, maintenance of electrical networks, use of lamp protectors and use of shielded motors, are basic and fundamental.

The moisture contained in the dust particles increases the ignition temperature. After ignition, air humidity has little effect on deflagration; however, there is a direct relationship between the moisture content, the minimum energy required for ignition, the minimum explosion concentration and particle dimensions. From a practical point of view, humidity cannot be considered an effective means of preventing explosions, as most ignition sources provide sufficient energy to heat and evaporate the moisture that may be present in the dust. For moisture to prevent explosion, the powder must be soaked.

Other preventive measures include electrical installations in explosion-proof silos, such as the enclosure of lamps and sockets; accurate control of relative air humidity (below 50%, a critical risk range); control of static electricity, through a silo grounding system; control of open flames with the use of welding equipment, matches and metal grinding operations, in addition to the installation of lightning rods.

Fungi are mainly responsible for the increase in temperature in grains stored with high humidity levels. The successions of species of fungi, bacteria and processes involved in heating the grain mass can be summarized as follows: (

)

Fires occur with all combustible dust, however, the amount of combustible material must be very large, and the particles must have little space between them, preventing direct and abundant contact with oxygen in the air. The particles must, however, be spaced apart, so that despite the existence of the ignition source and the consequent local combustion, the instantaneous propagation of the heat of combustion to the particles located in the innermost layers is not allowed, due to insufficient air. .

Ignition that occurs in a layer must be carefully controlled to prevent material deposited in structures, pipes and places that are difficult to see and clean from being placed in suspension, forming a dust cloud, which will evolve into an explosion. Layer fires are difficult to extinguish and can last for several hours after control.

• Access roads must be left for possible passage of fire engines;

• Electrical installations must be in good condition;

• Must contain a fire alarm system;

• It is advisable that the warehouse is periodically inspected by the fire department, who must be informed about the types of products stored;

• There must be different types of equipment to fight fire;

• A water containment system must be provided for in the construction of the tank;

• Packaging with combustible liquids, or with formulations containing flammable solvents, must be cooled with water mist, to avoid explosions;

• Fires can generate toxic vapors. Therefore, in these situations, it is important to avoid approaching any unprotected person.

Some measures can be taken to avoid the possibility of explosions in the storage plant.

Mineral oil: White mineral oil, when mixed with grains, changes the properties of the powder, favoring agglomeration among itself and with the grains. The use of white mineral oil reduces respirable dust by up to 95% and total dust by up to 75%, when all technical application parameters are met.

Preventive Operational Measures:

• Carefully clean the grain mass;

• Make continuous use of dust collection systems;

• Periodically clean the dust collection systems by changing the filters at the periods defined by the manufacturers;

• Clean the facilities, avoiding the accumulation of dust;

• Train operators and other employees regarding the potential risks of explosions;

• Carry out periodic maintenance of electro-mechanical equipment;

• Periodically certify the condition of electrical cables;

• Take due care when using welding equipment in maintenance services;

• Replace elevator buckets, conveyor blades and metal chains with plastic components.

Constructive aspects:

• Provide environments such as tunnels, galleries and grain loading and unloading points with dust collection systems;

• Install dust collection systems in elevators, buckets and grain transport pipes;

• Carry out electrical grounding of silos, electromechanical components and points that generate electrostatic charges;

• Design buildings that structurally include areas that are easy to rupture if explosions occur, this will minimize damage to the building, as the expanding gases will be released into the atmosphere;

• Install lightning rod systems;

• Install mineral oil sprinklers at points in the grain movement system that are likely to experience high concentrations of dust with values ​​greater than 0,05 kg/m3;

• Design lighting systems appropriate for environments at risk of explosions.

Federal Fluminense University

Federal University of Lavras

* Check out this article, with photos and tables, in PDF format. Just click using this link.

Cultivar Newsletter

Receive the latest agriculture news by email

access whatsapp group
Ascribe